Technical Information

 

The articles and information in this section are written by Johnk Engineering, Inc. and included for your general interest.  Please use them considerately. 

 

If you have any questions or comments about this information or would like to suggest new topics, please contact us at:

 

          Johnk Engineering, Inc.

          2226A Montgomery Avenue

          Cardiff by the Sea, CA 92007

          Phone  760-635-1385

          Telefax  760-635-1386

          Email  cbjohnk@inetworld.net

 

Index

1.       Cycling Operation of Circulating Fluidized Bed Boilers

2.     Fluidized Bed Grid Nozzle Designs (coming soon!)

3.     Petroleum Coke Firing in Circulating Fluidized Beds (coming soon!)

 

 

Cycling Operation of Circulating Fluidized Bed Boilers

 

This article is based on a presentation made at “The Sixth Foster Wheeler Fluidized Bed Customers’ Conference” on August 18, 2000, in San Diego, CA.

Introduction

 

The advent of deregulation of the U.S. power industry is leading to significant changes in the way circulating fluidized bed boilers (CFB’s) are being operated.  Prior to deregulation, most CFB’s were operated in a base-loaded mode.  The turbulent variations in power prices brought about by deregulation, however, are forcing many of these plants to carefully evaluate their plant operation and in many cases to operate in a cycling mode to maximize profits.  The key to survival for many of these plants is to “match generation to power pricing.” 

 

CFB’s have generally been operated in a base-loaded mode because they typically represent the state-of-the-art power generation technology in a system.  CFB boilers provide excellent combustion and emissions performance and typically replace or displace older, less efficient and dirtier boilers.  For any power generating system to reach its maximum performance it is necessary to ensure that the best technology is fully utilized at all times.  Older technology is only used as standby or auxiliary generation to make up requirements that the fully utilized “higher technology” cannot meet.

 

Another main reason for the traditional operation of CFB’s in a base-loaded mode is that many of the power contracts for independent power producers were written in compliance with governmental regulations meant to encourage development of the independent power industry.  In most cases, the contracts were long-term and at a relatively stable price.  In addition, the utilities generally had to accept nearly all of the generated power.  Many of these long term contracts are expiring and/or are undergoing changes due to the deregulation of the power industry.

 

So although most CFB operating experience has been with base-loaded operation, this not the whole story.  While the independent power producers were perfecting base load operation, the industrial and university power sectors were gaining experience with CFB cycling operation.  Both sectors have power and steam loads which can vary significantly - in university applications, boiler loads vary regularly during the day, as well as seasonally, while industrial operations tend to have varying boiler loads during the day as production increases or decreases with shift operation and also may have very rapid load swings if high energy consuming machinery is brought quickly on or off line.  Much of the knowledge needed to convert CFB’s to cycling operation comes from these two sources.

 

Converting to Cycling Operation

 

Conversion of CFB boiler operation from base-loaded to cycling requires significant changes for both the boiler operating staff and the boilers themselves.  Boiler operators of a base-loaded unit typically get the boiler set-up for full load operation early in the life of the boiler and then cruise at this altitude.  Boiler transient load operation - when boiler operation tends to be most problematical - generally provides only a minor inconvenience, because it does not occur frequently.  When operating in a cycling mode, however, the inconvenience of transient load operation becomes a major consideration, because of the increased frequency of the transients. 

 

With the introduction of cycling operation a boiler operator needs to understand the dynamics of transient load operation in his particular plant.  This includes the response of steam conditions, combustion and perhaps most importantly fluegas emissions to transient and part load operation, so that operation of the boiler is not jeopardized.  In most cases, operators will require training aimed at teaching them how to effectively manage the technical and financial aspects of CFB operation brought about by the conversion from base-load to cycling operation.

 

Most CFB’s were not specifically designed for cycling operation.  As a result, low or transient load is generally “on the edge” of the originally designed operating envelope.  Without control system or mechanical equipment modifications boilers converted to cycling operation may be unable to meet long term operating requirements.  In particular, the combustion and emissions processes are most affected by transient or low load operation. 

 

Each CFB installation is unique, because of the almost unlimited combinations of solid fuels, sorbents (for emissions control), regulated plant emissions levels, and steam conditions.  As multi-boiler CFB owners know, even identical boilers with identical fuels and sorbents tend to operate differently.  Operation of an already “unique” boiler at the edge of it’s operating envelope, magnifies it’s differences from other boilers.  What this means is that, although general principles apply (these will be explained later), every CFB boiler requires a unique approach when converting to cycling operation. 

 

When converting from base-loaded to cycling operation, the 3 most important issues are:

 

            How Low Can I Go? – What is the lowest operating load that can be reliably maintained and what can be done to reduce that minimum?  When the price received for selling power is less than what it costs to generate it, the lower the minimum operating load, the better.

 

            How Fast Can I Get There? – Once the minimum operating load is defined, the faster it can be reached, the more money can be saved.  This is probably less of a concern when cycling for cost savings than when trying to meet specific load requirements (as in industrial and university applications), but it is still important.

 

            What Is The Long Term Effect On My Boiler? – Thermal cycling of materials of construction affects the life cycle of all mechanical equipment. 

 

How Low Can I Go?

 

Although it has already been said that most CFB’s operate in a base-load mode at or near MCR, nearly all CFB boilers have been designed to operate as low as 35% MCR without auxiliary fuel firing.  Despite being designed for operation down to 35% MCR, most boilers control systems have not been tuned to operate frequently at or to transition smoothly to that load.  Experience with tuning CFB’s for part load operation down to 35% MCR indicates that although sometimes time consuming, the process is generally pretty painless.  The changes generally involve minor air curve modifications and proper setting of control loop parameters, and load indexing of gain and integral functions.

 

Several CFB’s have demonstrated the ability to operate satisfactorily at boiler loads down to 25% MCR.  Much more aggressive work with the control systems is typically required to reach these lower loads on a regular basis.  In many cases, operation this low will not be possible without modifications to the mechanical equipment.  In many CFB’s it may be possible to reach loads less than 25% MCR with physical modifications to the mechanical equipment.

 

Furnace temperature is the main issue when trying to define minimum operating load of a CFB.  In particular, insufficient furnace temperature is usually the problem.  At MCR load, the furnace temperature is typically between 1550°F and 1650°F with a relatively homogeneous temperature profile throughout the furnace and cyclone.  As load is reduced below MCR, the furnace temperature begins to sag with the temperature high in the furnace dropping more quickly than the temperature in the lower, refractory lined zone.  Somewhere between 50% - 70% MCR, the combustion airflow no longer decreases and becomes constant.  Decreasing the load further without decreasing airflow increases dramatically the rate of furnace temperature reduction. 

 

Furnace temperature at part load primarily affects or depends on the following:

 

            ·  Combustion Stability.  Because of the even bed temperatures and lack of a “flame” in a CFB, the furnace temperature needs to stay high enough to ensure that the fuel can reliably “auto combust”.  Fuel characteristics significantly affect the combustion process and thus the temperature required for stable combustion.  In general, at low temperatures high volatile fuels burn better than low volatile fuels and low ash fuels burn better than high ash fuels.  At the same time though, some low volatile fuels may actually burn better than high volatile fuels at low load, because of the specific combustion (and temperature) profile that they produce in the furnace.  The control system is typically set-up to define the minimum operating temperature as 1250°F, which is conservative for just about all.  In specific cases, proper testing and modification may allow for reduction in the minimum temperature.

 

            ·  Emissions.  Emissions generation and reduction reactions from a CFB are significantly affected by furnace temperature.  In general, the various fluegas emissions interact with each other and the interactions change with different furnace temperatures. 

 

-          CO increases with decreasing furnace temperature and boiler load.  Although CO generally is higher at lower loads, the increase above full load operation levels is usually minimal, because nearly all CO is combusted anyway due to the excess oxygen and high combustion residence time.  Low load CO emissions are fuel dependent with some fuels causing problems at low load.

-          NOx typically decreases with decreasing furnace temperatures.  NOx emissions are also sensitive to excess oxygen and tend to increase with increasing excess air (which typically increases as boiler load decreases).  If the boiler is equipped with a selective non-catalytic reduction (SNCR) system for NOx reduction, furnace temperature plays an even more important role, because the reduction reaction requires a higher temperature to be effective.  To maintain emissions at an acceptable level, the uncontrolled NOx emissions must drop off rapidly enough that the uncontrolled emission is less than the regulated level when the SNCR reaction becomes ineffective.  An additional complication is that NOx emissions tend to increase during transient load operation, because of a transiently high Ca/S ratio. 

-          SO2 control generally is optimized at moderate temperatures.  At high furnace temperatures (>1650°F) SO2 capture is reduced, because the limestone pores plug quickly with reactants preventing effective utilization of the entire surface area of the limestone particle.  At lower temperatures (<1400°F), the reduction reaction slows down also making SO2 removal less effective.  Both high and low furnace temperatures result in reduced SO2 removal efficiency, which can both fortunately usually be made up for by increasing the Ca/S ratio.  The difficulty is that increasing the Ca/S ratio has the unwanted effect of increasing NOx emissions. 

 

            ·  Excess Combustion Air.  Excess combustion air is typically constant from MCR down to 50%-70% MCR.  At that point, the combustion airflow generally stays constant as load decreases to maintain adequate fluidizing velocities and to minimize the chances of localized bed defluidization and bed agglomeration.  As the excess air increases, the furnace temperature drops rapidly because the ratio of cooling air (the excess air) to energy in the fuel (fuel feed rate) increases continuously.  The minimum airflows are typically set quite conservatively during boiler design and start-up.  Site specific testing and modifications have the potential to significantly reduce the minimum airflows and thus maintain a higher furnace temperature at minimum load. 

 

            ·  Fluidizing Grid Performance.  Performance of the fluidizing grid at low load is closely tied to excess air.  The tendency of a grid to plug or develop uneven airflow resulting in bed agglomerations ultimately determines minimum airflow (and thus excess air) that must pass through the nozzles.  Different nozzles have different pluggage characteristics.  Nozzles with a reduced tendency to plug can operate at lower airflows resulting in lower excess air and higher furnace temperatures (at low load).  Fuel ash characteristics also have an effect on grid performance, because uneven bed fluidization can be tolerated at low load, if a particular fuel has a lower tendency toward bed agglomeration or sintering.

 

            ·  Steam Conditions.  Furnace temperature and excess air work together to control the heat transfer to the superheaters.  Under certain conditions main steam temperatures may not be able to be met at part load.  This may or not be a concern for the turbine and boiler operation, but it needs to be taken into consideration.

 

In summary, the minimum stable operating load will be that at which the furnace temperature is adequate to maintain stable combustion while simultaneously maintaining fluegas emissions compliance and avoiding grid nozzle pluggage and bed agglomeration.

 

In some cases, the best course of action when trying to operate at low loads for more than about 4 hours may be to shut the boiler down hot.  There are typically no emissions problems when shutdown, and the operating costs are about as low as they can go without turning out the lights and sending everyone home.  The concept behind shutting down the boiler hot is to maintain as much heat in the boiler (both gas/solids and steam sides), so that a hot or warm restart can be quickly accomplished.  A CFB provides significant advantages over other combustion technologies in terms of hot or warm restarts, because the bed ash and relatively large refractory mass hold a large amount of heat and effectively insulate the boiler from heat loss. 

 

Typically hot restarts can be accomplished quickly if initiated within 8 hours after shutting off the boiler.  In many cases, all that is needed is an air purge (safety mandated) and the furnace temperature will still be high enough for immediate introduction of solid fuel.  In other cases a short period of time on auxiliary fuel will be required to bring the furnace temperature back up to the solid fuel firing permissive.  Shutdowns longer than about 8 hours will generally take longer to restart, because more heat will have been lost from the bed and have to be replaced during the restart process.  Twelve to eighteen hours is about the longest the boiler can be shutdown and still effectively perform a hot or warm restart of the boiler.

 

Hot shutdowns require operators that are specifically and well trained in shutting down and restarting the boiler hot.  All the operating decisions that typically can be made over a 12 hour period need to be made simultaneously when shutting down and restarting hot.  Every moment of indecision during a shutdown or restart means more heat lost and a longer restart time.  It is very important that clear operating guidelines be defined for the operators and that they fully know them and understand the reasoning behind the various operations. 

 

The main technical issues with shutting down and restarting hot are:

 

            ·  Greater Thermal Cycles on Refractory and Pressure Parts.  When shutting down and restarting the boiler, the thermal cycles of the mechanical equipment will be deeper than during simple cycling operation.  Some consideration, needs to be given to life of the refractory and pressure parts.

 

            ·  Fluidizing Grid Pluggage.  Certain types of fluidizing grid nozzles are prone to pluggage during shutdown and restart operation.  In these cases, the nozzles may need to be replaced with a non-plugging type if hot shutdowns/restarts are done on a frequent basis.

 

            ·  Bed Sintering.  Certain fuels may have a tendency to result in sintered bed ash when the boiler is shutdown hot.  High alkali and/or high sulfur fuels have the greatest tendency to agglomerate.  High ash fuels on the other hand generally have a lower tendency to bed sintering.  Most fuels will not have a sintering problem when shutdown hot, but bed sintering should be considered when making a decision to go to hot shutdown/restart operation.

 

How Fast Can I Get There?

 

Once the minimum load has been defined, the next question is how quickly the minimum load can be reached.  Although boiler load ramp rate is not as important when cycling for cost-reduction as when tracking an external load, it is still an important consideration.  There are many ways to define boiler load ramp rate, but unless they include some definition of allowable steam condition fluctuations they are relatively meaningless.  For the purposes of this discussion, the load ramp is defined as the maximum boiler load rate of change that results in maximum steam temperature and pressure fluctuations that will be considered acceptable to most IPP boiler owners.  The typical “out of the box” maximum ramp rate is about 4-5% MCR/min.  A load ramp rate of 2-3% MCR/min is more likely to meet “utility acceptable” criteria for maximum steam condition fluctuations.

 

The main concerns when determining the maximum load ramp rate are steam conditions and fluegas emissions.  As the boiler load demand is changed, it’s heat input needs to respond quickly to maintain the main steam conditions, especially pressure.  Proper control of steam conditions depends on proper tuning of the steam temperature and pressure control loops as well as the interface loop(s) with the turbine and extraction steam systems.  The shape of the CFB’s air curves and the tuning of the combustion air system also have a significant effect on the response of the boiler to load changes.  In general, boiler load changes are most dramatically affected by grid airflow changes.  The tuning of the airflow control loops has to be optimized to maintain the desired airflows when boiler load is changing. 

 

As the boiler responds to load demand changes by changing the firing rate, it affects the combustion conditions that generate emissions.  It is to be expected that fluegas emissions will experience significant transient variations during boiler load changes.  During a load reduction SO2 emissions will normally drop while NOx emissions will typically increase.  This is primarily a result of a high effective Ca/S during the load reduction as well as a lag in reduction of the excess air.  Conversely, when load is increased, SO2 will typically increase and NOx decrease, because of a low effective Ca/S.  Transient CO emissions are generally not a problem, unless the airflow control system is so poorly tuned that excess air drops to very low levels.  Set-up and tuning of the combustion air control system is essential for optimizing emissions performance during transient boiler operation.  Depending on the specific emissions requirements, various operating schemes can be developed to allow more rapid load changes by allowing certain emissions to climb for short periods and then being averaged with subsequently lower emissions to meet whatever time-averaged emissions are required.

 

Control system set-up and tuning for frequent transient operation is highly site specific.  Some of the things that will significantly affect the tuning are:  fuel characteristics, damper control, combustion air fan characteristics, turbine characteristics, emissions reduction systems and allowable emissions levels.

 

What Does It Do To My Boiler?

 

It is clear that cycling operation will have some detrimental effect on the life of a boiler.  Thermal cycling of nearly all materials of construction (primarily pressure parts and refractory in a boiler) results in transient differential thermal expansion causing undesirable stress in the materials.  In the case of pressure parts, the most significant stresses occur where different components are connected together.  At these connections, differential thermal expansion will tend to pull the connections apart or push them together deforming the metal.  In the case of refractory, either thin layers of refractory are expanding at a different rate than the pressure parts they are attached to or a thick refractory lining is expanding at different rates at different depths in the refractory.  In either case, the refractory will tend to develop cracks. 

 

It is generally accepted that normal cycling operation of a boiler has some effect on the boiler life, but in most properly designed boilers the reduction in life should be insignificant.  When operating in a hot shutdown/restart mode, the effect on boiler life will be more significant, because of the greater thermal changes experienced.  In either case, especially the hot shutdown/restart mode, it is recommended that the boiler manufacturer perform a review of the pressure part design to minimize the chance of experiencing any severe mechanical problems from frequent cycling.

 

Summary

 

As deregulation of the power industry continues the conversion of CFB boilers from base-loaded to cycling operation will become more common.  Although CFB’s have not traditionally been operated in a cycling mode, they have demonstrated very good performance under cycling conditions.  With the proper control system set-up and tuning and possibly some mechanical equipment modifications, nearly every CFB boiler can meet the owners expectations for efficient, clean and economical operation when operated as a load cycling plant.